Intrinsically safe type, non-addressable
type; multiple parallel connection S2004 Zener barrier and J-EI6032/EI6034 type
relay module are connected to EI series fire alarm controller and fire alarm
controller (linkage type).
	? Explosion-proof mark: ExibIICT6 Gb
	? The overhead light guide, the fire alarm
indicator 360 is visible.
	?Rotary detachable top cover design,
full-fitting patented structure, convenient for commissioning and maintenance.
	? A2 type detector with differential
temperature characteristics using an epoxy encapsulated NTC thermistor.
	? Ambient temperature: -10 °C to +50 °C
	? Ambient humidity: ≤95% RH
(non-condensing)
	? Operating voltage: powered by the safety
barrier
	? Action Temperature: 58 ° C
	? Confirmation light: normal monitoring,
green flashing; alarm, red steady;
	? Shell protection rating: IP30
	? Intrinsically safe explosion-proof
parameters: Ui: 28VDC Ii: 93mA Pi: 0.65W Ci: 0.02μF Li: 0mH
	? standby current:≤0.2mA
	? Protection area: 20m2
	? Wire system: two-wires, no polarity
	? Base mounting hole distance: 54mm ~ 78mm
	? Color: ivory white
	? Explosion-proof mark : ExibIICT6
? Associated equipment: S2004 type Zener barrier
	? Execution standard: GB 4716 ,《Point type heat detector》, GB3836.1-2010《Explosive environment 1 part: General requirements for equipment》, GB3836.4-2010 《Explosive environment Part
4: Intrinsically safe type “i "Protected Equipment》
 
                